Inhibited Transformer Oil INH-T2 5L

R385.00

Transformer Oil: Industrial and domestic transformers, meets ESKOM specifications. ESKOM quality.

SKU: F-GHINO910-C9A Categories: , Tag: Brand:

Inhibited Transformer Oil INH-T2 – 5L (Service/Top-Up Pack)

Premium inhibited transformer oil 5l for professional service work and top-ups. Meets IEC 60296:2020 (Inhibited). The product is PCB-free and has been Eskom tested (meets Eskom required parameters; pending final Eskom Approval).

Benefits at a glance

  • 73 kV dielectric strength (before treatment)
  • −47 °C pour point for cold-start reliability
  • Low moisture on delivery (9 ppm typical)
  • Non-corrosive; copper and sulphur tests pass

Typical Physical Characteristics (TDS)

Property Units Test Methods Typical Data
Visual Appearance Clear, Pale
Kinematic Viscosity @ 40 °C mm²/s ISO 3104 8.2
Viscosity Index ASTM D2270 115
Flash Point (COC) °C ISO 2719 178
Pour Point °C ISO 3016 −47
Density @ 20 °C kg/m³ ISO 12185 0.828
Breakdown Voltage (before treatment) kV IEC 60156 73
Dissipation Factor (DDF) @ 90 °C IEC 61156 <0.11
Resistivity @ 90 °C TΩ·m IEC 60247 >10
Interfacial Tension mN/m ASTM D971 44
Acidity mg KOH/g IEC 62021 0.01
Inhibitor Content W% IEC 60666 0.4%
Aromatic Content % IEC 60590 12
PCB Content IEC 61619 Not Detectable
Corrosive Copper ASTM D1275 Pass
Corrosive Sulphur DIN 51353 Pass
Water Content on Delivery ppm IEC 60814 9
Oil Quality Index (OQIN) 4400
Oxidation Stability h IEC 61125 Report
Gassing Tendency mm³/min ASTM D2300 Report
Furfural Content ppm IEC 61198 Report

Pack size: 5L. Also in 1L, 20L and 210L.

Weight 18.4 kg
Dimensions 287 × 225 × 390 mm
Shopping Cart